Seismic isolation unit
Control unit
- Water supply piping
- Cold and hot water piping
- Steam piping
- Oil piping Drainage piping
- Rainwater piping
- Ventilation piping
- Chemical piping
- Medical gas piping
- Food piping
- Please refer to “Product Drawings” and “Product Specifications” for detailed information such as materials of each part.
- Please refer to the “Installation Instructions” for installation procedures.
Applications and Features
Features
Space & cost saving
The use of a controller eliminates the need for hanging support for seismic isolation flexible cables.
This system is ideal when there are height restrictions from the ceiling.
Multiple pipes can be supported by a single controller, saving space & cost.
Things to note
- Both pipe lines shall be located as designed.
- Tighten bolt for flange diagonally & evenly.
- Both horses shall be located near by flexible joint.
- Building & ground side pipe material shall be SGP or more mechanically strong material.
- In case of polyvinyl chloride pipe, short pipe made of polyvinyl chloride lining on steel pipe is necessary for horse.
- When connect pipe, screw connection should avoid because of leakage risk. So, welding or flange connection are recommended.
- Each pipe shall be fixed to horse by means of 2 sets of U bolt as shown in drawing 4 or welding method.